HomeMy WebLinkAbout2010-12ORDINANCE NO. 2010-12
ADDING A NEW SECTION 10 -7 TO THE DANVILLE MUNICIPAL CODE
ADOPTING THE CALIFORNIA FIRE CODE (2010 EDITION), AS AMENDED
The Danville Town Council does ordain as follows:
SECTION 1. ADDING A NEW SECTION 10 -7 TO THE DANVILLE MUNICIPAL
CODE
A new Section 10 -7 is hereby added to the Danville Municipal Code to read as follows:
SECTION 10 -7
FIRE CODE
10 -7.1 Adoption.
The California Fire Code (2010 Edition) as adopted by the California State Fire Marshal,
incorporating by reference the International Fire Code (2009 Edition), and local
amendments adopted by the San Ramon Valley Fire Protection District through their
Ordinance No. 23, is hereby adopted with the following modifications to Ordinance No.
23:
(a) The following amendments and additions to the California Fire Code (2010
Edition) contained in San Ramon Valley Fire Protection District Ordinance No. 23 are
not ratified by the Town of Danville. In such cases, the underlying provisions of the
California Fire Code shall apply. Those provisions of Ordinance No. 23 not ratified
are:
- Section 902 is amended to add certain definitions and read as follows:
SUBSTANTIAL REMODEL. In existing buildings, any alteration that causes
additional floor area that is more than twenty -five percent (25 %) of the existing
floor area and where the total floor area exceeds 5000 square feet.
SUBSTANTIAL REMODEL, Group R -3. In an existing R -3 structure, any
alteration that causes additional floor area that exceeds fifty percent (50 %) of the
existing floor area and where the total floor area exceeds 5000 square feet.
- Section 903 is amended and reads as follows:
903.1 General. Automatic sprinkler systems shall comply with this section. For the
purposes of this section, fire walls shall not be considered as creating separate
buildings.
An automatic sprinkler system shall be provided for all new buildings with a gross
floor area that exceeds 5000 square feet and in the locations set forth in Section 903.
Exception: Group U occupancies.
903.2.1.1 Group A -1. An automatic sprinkler system shall be provided for Group A -1
occupancies where one of the following conditions exists:
1. The fire area exceeds 5000 square feet.
2. The fire area has an occupant load of 300 or more.
3. The fire area is located on a floor other than a level of exit discharge
serving such occupancies.
4. The fire area contains a multi - theatre complex.
903.2.1.3 Group A -3. An automatic sprinkler system shall be provided for Group A -3
occupancies where one of the following conditions exists:
1. The fire area exceeds 5000 square feet.
2. The fire area has an occupant load of 300 or more.
3. The fire area is located on a floor other than a level of exit discharge
serving such occupancies.
903.2.1.4 Group A -4. An automatic sprinkler system shall be provided for Group A -4
occupancies where one of the following conditions exists:
1. The fire area exceeds 5000 square feet
2. The fire area has an occupant load of 300 or more.
3. The fire area is located on a floor other than a level of exit discharge
serving such occupancies.
903.2.2.1 Group B. An automatic sprinkler system shall be provided for Group B
occupancies where one of the following conditions exists:
1. The fire area exceeds 5000 square feet.
903.2.3 Group E. Except as provided for in Section 903.2.3.1 for a new public school
campus an automatic sprinkler system shall be provided for Group E occupancies as
follows:
1. Throughout all Group E fire areas greater than 5000 square feet in area.
2. Throughout every portion of educational buildings below the lowest
level of exit discharge serving that portion of the building.
Exception: An automatic sprinkler system is not required in any
area below the lowest level of exit discharge serving that area
where every classroom throughout the building has at least one
exterior exit door at ground level.
PAGE 2 OF ORDINANCE NO. 2010-12
903.2.4 Group F -1. An automatic sprinkler system shall be provided throughout all
buildings containing a Group F -1 occupancy where one of the following conditions
exists:
1. A Group F -1 fire area exceeds 5000 square feet.
2. A Group F -1 fire area is located more than three stories above grade
plane.
903.2.7 Group M. An automatic sprinkler system shall be provided throughout
buildings containing a Group M occupancy where one of the following conditions
exists:
1. A Group M fire area exceeds 5000 square feet.
2. A Group M fire area is located more than three stories above grade
plane.
3. A Group M occupancy is used for the display and sale of upholstered
furniture.
903.2.9 Group S -1. An automatic sprinkler system shall be provided throughout all
buildings containing a Group S -1 occupancy where one of the following conditions
exists:
1. A Group S -1 fire area exceeds 5000 square feet
2. A Group S -1 fire area is located more than three stories above grade
plane.
903.2.9.1 Repair garages. An automatic sprinkler system shall be provided throughout
all buildings used as repair garages in accordance with Section 406 of the California
Building Code, as shown:
1. Buildings with a Repair Garage where the fire area exceeds 5000 square
feet.
2. Buildings with repair garages servicing vehicles parked in basements.
903.2.10 Group S -2 enclosed parking garages. An automatic sprinkler system shall be
provided throughout buildings classified as enclosed parking garages in accordance
with Section 406.4 of the California Building Code as follows:
1. Where the fire area of the enclosed parking garage exceeds 5000 square
feet; or
2. Where the enclosed parking garage is located beneath other occupancy
groups.
- Section 903.6.3 is added and reads as follows:
903.6.3 Substantial Remodel. In an existing building, if a substantial remodel occurs
the entire building shall be protected by an automatic sprinkler system in accordance
with section 903.
PAGE 3 OF ORDINANCE NO. 2010-12
- Section 903.6.3.1 is added and reads as follows:
903.6.3.1 Substantial Remodel, Group R -3. An automatic sprinkler system shall be
provided throughout all existing Group R -3 dwellings where a substantial remodel
occurs or where the gross floor area of the building exceeds 8,000 square feet,
Exception: When additional floor area does not exceed 1000 square feet.
- Section 1027.6 is amended to add a new section 1027.6.1 to read as follows:
1027.6.1 Exit discharge surface. Exterior exit pathway surfaces shall be suitable for
pedestrian use in inclement weather and terminate at a public way as defined in
the California Building Code.
SECTION 2. ENFORCING AGENCY.
The San Ramon Valley Fire Protection District shall administer and enforce the provisions
of this ordinance.
SECTION 3. CODIFICATION. Section 1 of this ordinance shall be codified in the
Danville Municipal Code.
SECTION 4. PUBLICATION AND EFFECTIVE DATE. The City Clerk shall have a
summary of this ordinance published twice in a newspaper of general circulation, once
within five (5) days before its adoption and once within fifteen (15) days after adoption.
This ordinance shall become effective thirty (30) days after adoption.
SECTION 5. SEVERABILITY. If any section, subsection, sentence, clause or phrase
of this ordinance is for any reason held to be invalid, such decision shall not affect the
validity of the remaining portions of the ordinance. The Danville Town Council hereby
declares that they would have adopted the ordinance, and each section, subsection,
sentence, clause, or phrase thereof, irrespective of the fact that one or more sections,
subsections, sentences, clauses or phrases was declared invalid.
PAGE 4 OF ORDINANCE NO. 2010-12
The foregoing Ordinance was introduced on November 16, 2010 and approved and
adopted by the Danville Town Council at a regular meeting held on December 21, 2010,
by the following vote:
AYES: Stepper, Andersen, Arnerich, Doyle, Storer
NOES: None
ABSTAIN: None
ABSENT: None
APPROVED AS T FORM:
CITY ATTORNEY
CLERK'S CERTIFICATE
I, Marie Sunseri, City Clerk of the Town of Danville, hereby certify that the foregoing is
a true and accurate copy of Ordinance No. 2010 -12 of said Town and that said
ordinance was published according to law.